Quantcast
Channel: Gold Coast Solar Power Solutions
Viewing all articles
Browse latest Browse all 206

Xantrex Solar Inverter Fault & Error Messages

$
0
0

Xantrex Solar InverterXantrex solar inverters were originally made by a Canadian company but have since been bought out by Schneider Electric.  A few years ago, they discontinued the Xantrex model and introduced the Context range to replace it.  So when a Xantrex solar inverter fails under warranty, it is replaced with the new Schneider.

In case you see an issue with a Xantrex solar inverter and it’s outside the 5-year warranty, we have put together a list of faults and solutions from its users manual. The list contains procedures for solving possible problems and provides you with solutions. Should you decide to follow the recommended actions, please note that safety measures should be observed to avoid any risk of injury. Otherwise, contact a qualified electrician for assistance.

Problem

Possible Cause

Solution

The inverter’s LEDs and display are
blank and the inverter does not
operate in sufficient sunlight.
Utility service panel AC and DC
breakers are switched off
Turn on the breakers in the sequence described in “Commissioning
Procedure” below.
The display reads Inverter Offline
and AC Voltage Fault.
Utility service panel breakers are
switched off.
AC grid voltage is not present or
incorrect.
Turn on utility panel breakers.
Check AC connections at the
inverter’s terminals. Ensure AC
voltage within the range specified in “Output” below is present.
The display reads Inverter Offline
with sufficient sunlight.
DC breakers are switched off (if
installed), or DC fuses are blown (if
installed).
DC array voltage is not present.
Turn on any DC breakers and check any DC fuses.
Check DC connections at the
inverter’s positive and negative DC terminals. Check for incorrectly wired PV arrays.
The display reads Inverter Offline
and DC Voltage Fault with sufficient
sunlight.
DC voltage is present but incorrect. Check DC connections at the
inverter’s positive and negative DC terminals. Check for incorrectly wired PV arrays. Ensure a voltage within the operating voltage range is
present at the inverter’s terminals.
Only the inverter RED LED is
illuminated and the display reads
Ground Fault.
Ground fault condition detected on
the PV array
The PV system should be checked by a qualified electrician and repaired. See “PV Ground Fault Detection” on page viii. To reconnect:
1. Make sure the GT Inverter is not outputting power, and then
switch off the DC breaker. If a
DC breaker is not used, then
disconnect the DC input.
2. Switch off the AC breaker.
3. Remedy the actual ground fault.
4. Restart the unit using the
sequence described in
“Commissioning Procedure” below.
The System value (power being
produced by the system) displayed
on each inverter’s LCD is different
on inverters connected to the same
daisy-chained network.
Inverters can display different
System values when one of the
inverters is set to a different baud
rate than the rest. That particular
inverter’s baud rate screen shows Tx
and/or Rx error (see Table 5-3 on
page 5–6).
Check each inverter’s baud rate and compare the settings. Change any inverters with an incorrect baud rate.
Make sure to follow the
recommended procedure supplied by Xantrex. See the Application Note,
Xantrex Grid Tie Solar Inverter
Baud Rate Change Procedure
(976-0216-01-01 available on
www.xantrex.com).

 

Here are the steps of the Commissioning Procedure:

To start the GT Inverter:
1. Ensure the AC breaker is off.
2. Ensure the correct multi-contact PV connectors are firmly plugged into the GT Inverter as described in “Connecting the DC Wiring” on page 3–2 of the Xantrex Solar Inverter manual.
3. (GT 2.8-AU only) Ensure the AC quick connect is firmly inserted into the GT Inverter and that the coupling ring is tight.
4. Uncover the PV array and/or close the main DC disconnect switch, if one is installed. Ensure the PV array is producing the required output voltage.
5. Connect the utility grid voltage by switching the AC circuit breaker on.

The AC Voltage should be within below Output range:

GT2.8-AU  GT5.0-AU
Maximum output power 2800 W ac  5000 W ac
Maximum output current  14.0 A 24.0 A
Nominal grid voltage 230 Vac
Nominal grid frequency 50 Hz
Total Harmonic Distortion (THD) <3%
Power factor >0.99% (at rated power)
>0.95% (full power range)
Output characteristics Current source
Output current waveform Sine wave

If you need to check the full details, you can find them on the Xantrex solar inverter manual’s Troubleshooting section.  Should you follow the troubleshooting steps above but the issue is not fixed on your Xantrex solar inverter check if it’s still within the warranty period so you can contact the equipment installer or supplier.

If your Xantrex solar inverter is outside the warranty period we suggest that you contact a professional solar power expert. If you’re in the Gold Coast or Brisbane area contact Gold Coast Power Solutions here and we will be in touch to provide you with further assistance.

Need a quality solar inverter? We deliver Australia wide
Got A Question About Solar Power? Click Here For Answers!

The post Xantrex Solar Inverter Fault & Error Messages appeared first on Gold Coast Solar Power Solutions.


Viewing all articles
Browse latest Browse all 206

Trending Articles